Table 1—Physical Data 551B

BASE UNIT 551B

036

048

060

072

NOMINAL CAPACITY (nominal tons)

3

4

5

6

OPERATING WEIGHT (lb)

Unit

435

445

465

540

Perfect Humidity™ Adaptive Dehumidification System

15

23

25

29

EconoMi$er IV

50

50

50

50

Roof Curb

115

115

115

115

COMPRESSOR

Scroll

Quantity

1

1

1

1

Oil (oz)

42

53

50

60

REFRIGERANT TYPE

R-22

Expansion Device

Acutrol™ Metering Device

Operating Charge (lb-oz)

Standard Unit

5-8

10-2

10-0

12- 8

Unit With Perfect Humidity Adaptive Dehumidification System

12-5

18-8

20-5

23-14

CONDENSER FAN

Propeller

Quantity...Diameter (in.)

1...22

1...22

1...22

1...22

Nominal Cfm

3500

3500

4100

4100

Motor Hp...Rpm

1

/8...825

1

/8...825

1

/

4

...1100

1

/

4

...1100

Watts Input (Total)

180

180

320

320

CONDENSER COIL

3/8---in. OD Enhanced Copper Tubes, Aluminum Lanced Fins

Rows...Fins/in.

1...17

2...17

2...17

2...17

Total Face Area (sq ft)

14.6

16.5

16.5

21.3

EVAPORATOR COIL

3/8---in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins

Standard Unit

Rows...Fins/in.

2...15

2...15

4...15

4...15

Total Face Area (sq ft)

5.5

5.5

5.5

7.3

Unit with Perfect Humidity Adaptive Dehumidification System

Rows...Fins/in.

1...17

2...17

2...17

2...17

Total Face Area (sq ft)

3.9

3.9

3.9

5.2

EVAPORATOR FAN

Centrifugal Type, Belt Drive

Quantity...Size (in.)

1...10 x 10

1...10 x 10

1...10 x 10

1...10 x 10

Nominal Cfm

1200

1600

2000

2400

Maximum Continuous Bhp

Std

1.20

1.20

1.30/2.40*

2.40

Hi-Static

2.40

2.40

2.90

2.90

Motor Frame Size

Std

48

48

56

56

Hi-Static

56

56

56

56

Fan Rpm Range

Std

680-1044

770-1185

1035-1460/1035---1460*

1120-1585

Hi-Static

1075-1455

1075-1455

1300-1685

1300-1685

Motor Bearing Type

Ball

Ball

Ball

Ball

Maximum Fan Rpm

2100

2100

2100

2100

Motor Pulley Pitch Diameter A/B (in.)

Std

1.9/2.9

1.9/2.9

2.4/3.4

2.4/3.4

Motor Pulley Pitch Diameter A/B (in.)

Hi-Static

2.8/3.8

2.8/3.8

3.4/4.4

3.4/3.4

Nominal Motor Shaft Diameter (in.)

Std

1/2

1

/

2

5

/

8

5

/

8

Hi-Static

5

/

8

5

/

8

7

/

8

7

/

8

Fan Pulley Pitch Diameter (in.)

Std

4.5

4.0

4.0

3.7

Hi-Static

4.5

4.5

4.5

4.5

Belt — Type...Length (in.)

Std

1...A...36

1...A...36

1....4...40

1...A...38

Hi-Static

1...A...39

1...A...39

1...A...40

1...A...40

Pulley Center Line Distance (in.)

10.0-12.4

10.0-12.4

14.7-15.5

14.7-15.5

Speed Change per Full Turn of

Std

65

70

75

95

Speed Change per Full Turn of

Movable Pulley Flange (rpm)

Hi-Static

65

65

60

60

Movable Pulley Maximum Full

Std

5

5

6

5

Movable Pulley Maximum Full

Turns from Closed Position

Hi-Static

6

6

5

5

Factory Setting — Full Turns Open

Std

3

3

3

3

Hi-Static

3

1

/

2

3

1

/

2

3

1

/

2

3

1

/

2

Factory Speed Setting (rpm)

Std

826

936

1248

1304

Hi-Static

1233

1233

1396

1396

Fan Shaft Diameter at Pulley (in.)

5

/

8

5

/

8

5

/

8

5

/

8

HIGH-PRESSURE SWITCH (psig)

Standard Compressor Internal Relief

450 ± 50

Cutout

428

Reset (Auto.)

320

LOSS-OF-CHARGE/LOW-PRESSURE

SWITCH (Liquid LIne) (psig)
Cutout

7 ± 3

Reset (Auto.)

22 ± 5

FREEZE PROTECTION THERMOSTAT

Opens (F)

30

Closes (F)

45

OUTDOOR-AIR INLET SCREENS

Cleanable. Screen quantity and size varies with option selected.

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

2...16 x 25 x 2

2...16 x 16 x 2