Bosch BOSCH OVEN User Manual

Page 11

Advertising
background image

English 9

length/ slack has been adjusted, attach strain relief per instructions included with
strain relief.

Warning: To prevent electrical shock, the grounding prong on the range

cord should not be cut or removed under any circumstances. It must be plugged
into a matching grounding type receptacle and connected to a correctly polarized
240- Volt circuit. If there is any doubt as to whether the wall receptacle is properly
grounded, have it checked by a qualified electrician.

Figure 8: Strain Relief Knockout

Figure 9: Grounding Requirements

Tip: The knockout panel below the terminal block can be removed from
the range to install the strain relief: Remove knockout panel from range,
install strain relief in panel and reattach. DO NOT remove entire range
back panel.

Warning: Risk of Electric Shock or Fire. Frame grounded to neutral

through a ground strap. Grounding through the neutral conductor is prohibited
for new branch-circuit installations (1996 NEC), mobile homes, and recreational
vehicles, or in an area where local codes prohibit grounding through the neutral
conductor.

For installations where grounding through the neutral conductor is prohibited,
(a) disconnect the link from the neutral, (b) use grounding terminal or lead to
ground unit, (c) connect neutral terminal to lead branch circuit neutral in usual
manner (when the appliance is to be connected by means of a cord kit, use 4-
conductor cord for this purpose).

Use only cord kits rated 125/250 volts (minimum), 40 or 50 amperes (depend-
ing on local code) and labeled “For Use with Ranges”. Strain relief provided
with cord must be installed per instructions

Advertising