Cooling capacities (cont) – Bryant 581C User Manual

Page 185

Advertising
background image

185

PERFORMANCE DATA — 579F (cont)

COOLING CAPACITIES (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F216 (18 Tons)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

5400

6000

Evaporator Air — Ewb (F)/BF

54/0.49

58/0.31

62/0.20

67/0.18

72/0.16

76/0.19

80/0.05

54/0.53

58/0.35

62/0.23

67/0.19

72/0.17

76/0.19

80/0.05

75

TC

194

198

206

223

243

260

277

200

203

210

227

246

263

—

SHC

194

178

169

146

121

99

79

200

191

177

152

125

102

—

kW

13.6

13.7

13.9

14.2

14.6

15.0

15.2

13.7

13.8

14.0

14.4

14.7

15.1

—

85

TC

189

192

200

217

235

252

269

195

195

204

220

239

255

—

SHC

189

176

166

143

118

97

76

195

195

174

149

123

100

—

kW

15.1

15.2

15.4

15.9

16.3

16.6

16.9

15.3

15.3

15.7

16.0

16.4

16.8

—

95

TC

183

184

193

209

227

243

—

189

190

196

212

230

246

—

SHC

183

181

162

140

115

94

—

189

190

170

146

120

97

—

kW

16.8

16.8

17.1

17.6

18.0

18.4

—

17.0

17.0

17.2

17.6

18.1

18.5

—

105

TC

177

178

185

201

218

234

—

183

185

189

204

221

237

—

SHC

177

178

159

137

112

91

—

183

185

166

143

116

94

—

kW

18.6

18.6

18.8

19.3

19.8

20.2

—

18.8

18.6

18.9

19.4

19.9

20.3

—

115

TC

171

171

177

192

209

224

—

176

177

181

195

212

226

—

SHC

171

171

154

133

109

88

—

176

177

161

139

113

90

—

kW

20.5

20.5

20.7

21.2

21.8

22.1

—

20.7

20.7

20.8

21.3

21.8

22.2

—

117

TC

170

170

176

191

207

222

—

175

175

180

193

210

224

—

SHC

170

170

154

132

108

87

—

175

175

160

138

112

90

—

kW

20.9

20.9

21.1

21.6

22.1

22.5

—

21.1

21.1

21.2

21.7

22.2

22.6

—

120

TC

168

168

173

188

204

—

—

173

173

177

191

207

—

—

SHC

168

168

152

131

107

—

—

173

173

159

137

111

—

—

kW

21.5

21.5

21.7

22.2

22.7

—

—

21.7

21.7

21.8

22.3

22.8

—

—

579F216 (18 Tons) (cont)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

7000

8000

Evaporator Air — Ewb (F)/BF

54/0.58

58/0.42

62/0.29

67/0.21

72/0.20

76/0.20

80/0.05

54/0.62

58/0.48

62/0.36

67/0.23

72/0.22

76/0.21

80/0.04

75

TC

209

209

215

232

251

268

—

216

217

221

236

255

272

—

SHC

209

209

189

162

132

106

—

216

217

198

171

138

109

—

kW

13.9

13.9

14.1

14.5

14.9

15.2

—

14.1

14.1

14.2

14.5

15.0

15.3

—

85

TC

203

204

209

224

243

260

—

211

211

215

228

247

263

—

SHC

203

204

185

159

129

103

—

211

211

192

168

135

107

—

kW

15.5

15.5

15.7

16.1

16.5

16.9

—

15.7

15.7

15.8

16.2

16.6

17.0

—

95

TC

197

197

202

216

235

251

—

204

204

209

220

238

254

—

SHC

197

197

180

156

126

100

—

204

204

185

165

132

104

—

kW

17.2

17.2

17.4

17.8

18.2

18.7

—

17.4

17.4

17.6

17.9

18.3

18.7

—

105

TC

191

191

195

208

225

241

—

197

197

202

211

228

244

—

SHC

191

191

175

152

123

97

—

197

197

177

161

128

100

—

kW

19.0

19.0

19.2

19.5

20.0

20.5

—

19.2

19.2

19.3

19.6

20.1

20.6

—

115

TC

184

184

188

199

215

230

—

190

190

194

202

218

—

—

SHC

184

184

168

149

119

94

—

190

190

170

158

125

—

—

kW

21.0

21.0

21.1

21.5

22.0

22.4

—

21.1

21.1

21.2

21.6

22.1

—

—

117

TC

183

183

187

197

214

228

—

188

188

192

200

216

—

—

SHC

183

183

166

148

118

93

—

188

188

171

157

124

—

—

kW

21.3

21.4

21.5

21.8

22.4

22.7

—

21.5

21.5

21.7

22.0

22.5

—

—

120

TC

180

180

185

194

210

—

—

186

186

190

197

—

—

—

SHC

180

180

163

147

117

—

—

186

186

172

156

—

—

—

kW

21.9

22.0

22.1

22.4

23.0

—

—

22.1

22.1

22.2

22.5

—

—

—

BF

—

Bypass Factor

Edb

—

Entering Dry-Bulb

Ewb

—

Entering Wet-Bulb

kW

—

Compressor Motor Power Input

ldb

—

Leaving Dry-Bulb

lwb

—

Leaving Wet-Bulb

SHC

—

Sensible Heat Capacity (1000 Btuh) Gross

TC

—

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

–

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

–

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

0.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

0.10

0.98

1.96

2.94

3.92

4.91

0.20

0.87

1.74

2.62

3.49

4.36

0.30

0.76

1.53

2.29

3.05

3.82

0.40

0.65

1.31

1.96

2.62

3.27

0.50

0.55

1.09

1.64

2.18

2.73

0.60

0.44

0.87

1.31

1.74

2.18

0.70

0.33

0.65

0.98

1.31

1.64

579

F18

0

-300