PERFORMANCE DATA — 579F (cont)

COOLING CAPACITIES (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F240 (20 Tons)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

6,000

7,000

Evaporator Air — Ewb (F)/BF

54/0.48

58/0.31

62/0.21

67/0.19

72/0.17

76/0.22

80/0.05

54/0.54

58/0.37

62/0.25

67/0.21

72/0.19

76/0.21

80/0.04

75

TC

217

222

232

252

274

294

316

227

231

238

254

281

297

322

SHC

217

199

189

163

136

112

90

227

217

202

172

143

115

91

kW

15.1

15.2

15.4

15.8

16.2

16.6

17.0

15.3

15.4

15.5

15.9

16.4

16.5

17.2

85

TC

212

217

226

244

266

285

306

222

225

231

250

272

291

312

SHC

212

194

185

159

133

109

87

222

211

198

170

140

113

88

kW

16.9

17.2

17.3

17.6

18.0

18.4

18.8

17.1

17.3

17.3

17.7

18.2

18.6

19.0

95

TC

206

208

217

236

257

276

295

215

216

223

241

262

281

301

SHC

206

197

181

156

129

106

84

215

213

194

166

136

110

84

kW

18.9

18.8

19.0

19.5

20.0

20.4

20.8

19.0

19.0

19.2

19.6

20.1

20.5

21.0

105

TC

199

202

209

227

247

265

285

208

209

215

232

252

270

—

SHC

199

190

177

152

126

103

80

208

209

189

163

132

107

—

kW

20.8

20.9

21.1

21.6

22.0

22.5

22.9

21.0

21.0

21.2

21.7

22.2

22.6

—

115

TC

192

194

200

218

237

254

—

202

202

207

222

242

259

—

SHC

192

192

173

149

122

99

—

202

202

183

159

129

103

—

kW

23.0

22.9

23.3

23.8

24.3

24.8

—

23.2

23.2

23.5

23.9

24.5

24.9

—

117

TC

191

191

199

216

235

252

—

200

200

205

220

240

257

—

SHC

191

191

172

148

121

99

—

200

200

182

158

128

102

—

kW

23.5

23.5

23.7

24.2

24.8

25.2

—

23.8

23.8

23.9

24.4

24.9

25.3

—

120

TC

189

189

196

213

232

249

—

197

198

203

217

236

—

—

SHC

189

189

170

147

120

98

—

197

198

181

156

127

—

—

kW

24.2

24.2

24.4

25.0

25.5

25.9

—

24.5

24.5

24.6

25.1

25.6

—

—

579F240 (20 Tons) (cont)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

8,000

9,000

Evaporator Air — Ewb (F)/BF

54/0.58

58/0.43

62/0.30

67/0.23

72/0.21

76/0.22

80/0.04

54/0.62

58/0.48

62/0.35

67/0.24

72/0.23

76/0.23

80/0.04

75

TC

236

238

241

259

286

302

328

244

244

250

267

290

307

—

SHC

236

232

211

181

149

119

91

244

244

222

192

155

123

—

kW

15.5

15.5

15.6

15.9

16.5

16.6

17.3

15.7

15.7

15.8

16.1

16.6

16.7

—

85

TC

231

230

237

254

276

296

—

237

238

243

258

281

300

—

SHC

231

230

209

179

146

117

—

237

238

216

189

152

121

—

kW

17.5

17.3

17.4

17.8

18.3

18.7

—

17.5

17.6

17.6

18.0

18.4

18.8

—

95

TC

223

223

229

245

267

285

—

231

230

235

249

270

289

—

SHC

223

223

203

176

142

114

—

231

230

209

185

148

117

—

kW

19.2

19.2

19.3

19.8

20.2

20.6

—

19.5

19.4

19.5

19.8

20.3

20.8

—

105

TC

216

216

221

236

256

274

—

222

223

228

239

260

278

—

SHC

216

216

197

172

139

110

—

222

223

202

181

145

114

—

kW

21.3

21.3

21.4

21.8

22.3

22.7

—

21.4

21.5

21.6

21.9

22.4

22.8

—

115

TC

208

209

213

226

246

263

—

214

214

220

229

249

266

—

SHC

208

209

190

168

135

107

—

214

214

193

177

141

110

—

kW

23.5

23.5

23.7

24.0

24.6

25.0

—

23.7

23.7

23.9

24.2

24.7

25.1

—

117

TC

207

207

212

224

243

260

—

213

213

219

227

246

263

—

SHC

207

207

188

167

134

106

—

213

213

191

176

140

109

—

kW

24.0

24.0

24.1

24.5

25.0

25.5

—

24.2

24.2

24.2

24.6

25.1

25.6

—

120

TC

204

205

209

221

240

—

—

210

210

215

224

243

—

—

SHC

204

205

185

166

133

—

—

210

210

193

175

139

—

—

kW

24.7

24.7

24.8

25.2

25.7

—

—

24.9

24.9

25.0

25.3

25.8

—

—

BF

—

Bypass Factor

Edb

—

Entering Dry-Bulb

Ewb

—

Entering Wet-Bulb

kW

—

Compressor Motor Power Input

ldb

—

Leaving Dry-Bulb

lwb

—

Leaving Wet-Bulb

SHC

—

Sensible Heat Capacity (1000 Btuh) Gross

TC

—

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

–

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

–

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

0.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

0.10

0.98

1.96

2.94

3.92

4.91

0.20

0.87

1.74

2.62

3.49

4.36

0.30

0.76

1.53

2.29

3.05

3.82

0.40

0.65

1.31

1.96

2.62

3.27

0.50

0.55

1.09

1.64

2.18

2.73

0.60

0.44

0.87

1.31

1.74

2.18

0.70

0.33

0.65

0.98

1.31

1.64

579