Cooling capacities (cont) – Bryant 581C User Manual

Page 188

Advertising
background image

188

PERFORMANCE DATA — 579F (cont)

COOLING CAPACITIES (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F240 (20 Tons) (cont)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

10,000

Evaporator Air — Ewb (F)/BF

54/0.65

58/0.52

62/0.40

67/0.26

72/0.24

76/0.24

80/0.04

75

TC

250

250

256

267

294

314

—

SHC

250

250

227

200

161

127

—

kW

15.8

15.8

15.9

16.1

16.7

17.1

—

85

TC

243

244

249

262

284

303

—

SHC

243

244

220

198

158

124

—

kW

17.6

17.8

17.7

18.0

18.5

18.9

—

95

TC

236

236

241

252

274

292

—

SHC

236

236

212

194

154

121

—

kW

19.5

19.5

19.7

19.9

20.4

20.9

—

105

TC

228

228

234

242

263

281

—

SHC

228

228

203

190

151

117

—

kW

21.6

21.6

21.8

22.0

22.5

22.9

—

115

TC

220

220

223

232

251

268

—

SHC

220

220

207

186

147

113

—

kW

23.9

23.9

23.9

24.2

24.7

25.2

—

117

TC

218

218

221

230

249

266

—

SHC

218

218

205

185

146

112

—

kW

24.3

24.3

24.4

24.7

25.2

25.6

—

120

TC

215

215

218

226

245

—

—

SHC

215

215

203

183

145

—

—

kW

25.1

25.1

25.1

25.4

25.9

—

—

BF

—

Bypass Factor

Edb

—

Entering Dry-Bulb

Ewb

—

Entering Wet-Bulb

kW

—

Compressor Motor Power Input

ldb

—

Leaving Dry-Bulb

lwb

—

Leaving Wet-Bulb

SHC

—

Sensible Heat Capacity (1000 Btuh) Gross

TC

—

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

–

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

–

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

0.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

0.10

0.98

1.96

2.94

3.92

4.91

0.20

0.87

1.74

2.62

3.49

4.36

0.30

0.76

1.53

2.29

3.05

3.82

0.40

0.65

1.31

1.96

2.62

3.27

0.50

0.55

1.09

1.64

2.18

2.73

0.60

0.44

0.87

1.31

1.74

2.18

0.70

0.33

0.65

0.98

1.31

1.64