PERFORMANCE DATA — 579F (cont)

COOLING CAPACITIES (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F216 (18 Tons) (cont)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

9000

Evaporator Air — Ewb (F)/BF

54/0.65

58/0.53

62/0.40

67/0.25

72/0.23

76/0.23

80/0.05

75

TC

223

223

228

239

258

275

—

SHC

223

223

202

181

144

113

—

kW

14.3

14.3

14.4

14.6

15.0

15.4

—

85

TC

216

217

222

231

250

266

—

SHC

216

217

194

177

141

110

—

kW

15.8

15.9

16.0

16.3

16.7

17.1

—

95

TC

210

210

215

223

241

257

—

SHC

210

210

187

174

138

107

—

kW

17.6

17.6

17.7

18.0

18.4

18.8

—

105

TC

202

202

207

214

231

—

—

SHC

202

202

184

170

134

—

—

kW

19.4

19.4

19.5

19.7

20.2

—

—

115

TC

195

195

196

204

221

—

—

SHC

195

195

192

166

131

—

—

kW

21.3

21.3

21.4

21.7

22.2

—

—

117

TC

193

193

194

202

219

—

—

SHC

193

193

192

166

130

—

—

kW

21.7

21.7

21.7

22.0

22.6

—

—

120

TC

191

191

191

199

—

—

—

SHC

191

191

191

164

—

—

—

kW

22.3

22.3

22.3

22.6

—

—

—

BF

—

Bypass Factor

Edb

—

Entering Dry-Bulb

Ewb

—

Entering Wet-Bulb

kW

—

Compressor Motor Power Input

ldb

—

Leaving Dry-Bulb

lwb

—

Leaving Wet-Bulb

SHC

—

Sensible Heat Capacity (1000 Btuh) Gross

TC

—

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

–

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

–

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

0.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

0.10

0.98

1.96

2.94

3.92

4.91

0.20

0.87

1.74

2.62

3.49

4.36

0.30

0.76

1.53

2.29

3.05

3.82

0.40

0.65

1.31

1.96

2.62

3.27

0.50

0.55

1.09

1.64

2.18

2.73

0.60

0.44

0.87

1.31

1.74

2.18

0.70

0.33

0.65

0.98

1.31

1.64