Calibration

62

CAFSPro User Operation Manual

p/n: 029-0020-75-0

3.

Once the password is entered the unit displays FAC and returns to nor-
mal operation. (See Figure 8-2: ‘Sample PASS Display’ on page 61.)

8.2

CALIBRATION

WARNING !

WHEN ENTERING THE CALIBRATION MODE, THE PUMP MUST BE SET UP
FOR PUMPING WATER AND THE PUMP MUST BE ENGAGED. BEFORE
ENTERING A CALIBRATION PASSWORD MAKE SURE THE ENGINE IS AT
“IDLE.”

THE FIRST THREE DISPLAYS AFTER ENTERING THE CALIBRATION MODE
ARE AIRFLOW CALIBRATION SETTINGS. THESE VALUES DO NOT
REQUIRE ADJUSTMENT. CHANGING THESE VALUES COULD RESULT IN
THE SYSTEM “RUNNING” AWAY AND BEING OVER PRESSURIZED.

IF ANY OF THE AIRFLOW DISPLAY VALUES REQUIRE ADJUSTMENT CON-
SULT THE FACTORY.

To Begin...

To disengage the CAFSPro compressor,

1.

With the pump in gear (shift to PUMP), press and hold the ON pad to
disengage the air compressor.

2.

The display shows OFF3..OFF2..OFF1 and the alarm beeps.

3.

With the CAFSPro system OFF, the CAFSPro display shows OFF.

4.

It is now safe to proceed with CAFSPro water flow calibration.

Water Flow Calibration

(See Figure 8-2: ‘Sample PASS Display’ on page 61.) Also see Figure 4-4:
“Sample, Display ICONS” on page 34.

Both the CAFSPro and FoamLogix displays require calibration when the
system has been repaired or modified in a way that affects these readings.

1.

On the CAFSPro display, press and hold the DISPLAY (

i

) pad.