d. See Fig.10 for typical connections. Each SmartBox

zone can control two heaters.

FIG. 10

Connecting the building controller’s heating contacts to the
SmartBox

(for contact closure).

Connect to the red leads as shown in Fig.11. These are
not powered contacts.
-- Remove the wiring from the heat contacts (one for

each zone) in the room controller.

-- Connect these same contacts to the SmartBox

Enable wiring Zone 1 and Zone 2, and to common
Zone 1 and Zone 2.

- This allows each SmartBox

zone

to operate within the temperature
parameters of the room controller.

FIG. 11

Connecting the SmartBox

temperature sensors

Connect 18 gauge 2 wire stranded cable between the
t h e g r ay l e a d s a s s h ow n i n F i g .1 2 a n d t h e
SmartBoxsensor. See page 6 for sensor location.

Solder the connection between the SmartBox

sensor

and the 2 wire conductor. Wrap this connection with
electrical tape.

Use only the L.B.White SmartBox

sensors, part

number 572815, provided with the SmartBox

, or

order replacements as needed. Do not use sensors
from room controllers as these are not compatible with
the L.B.White SmartBox

.

FIG. 12

8

WIRING FROM

Smart Box™

TO

Smart Sense™

VARIABLE RATE GAS CONTROL VALVE

VOL

TS T

O V

AL

VE

VA

LV

E

HEATER 1
GAS VALVE

HEATER 2
GAS VALVE