d. See Fig.10 for typical connections. Each SmartBox

™

zone can control two heaters.

FIG. 10

Connecting the building controller’s heating contacts to the
SmartBox

™

(for contact closure).

Connect to the red leads as shown in Fig.11. These are
not powered contacts.
-- Remove the wiring from the heat contacts (one for

each zone) in the room controller.

-- Connect these same contacts to the SmartBox

™

Enable wiring Zone 1 and Zone 2, and to common
Zone 1 and Zone 2.

- This allows each SmartBox

™

zone

to operate within the temperature
parameters of the room controller.

FIG. 11

Connecting the SmartBox

™

temperature sensors

Connect 18 gauge 2 wire stranded cable between the
t h e g r ay l e a d s a s s h ow n i n F i g .1 2 a n d t h e
SmartBox™sensor. See page 6 for sensor location.

Solder the connection between the SmartBox

™

sensor

and the 2 wire conductor. Wrap this connection with
electrical tape.

Use only the L.B.White SmartBox

™

sensors, part

number 572815, provided with the SmartBox

™

, or

order replacements as needed. Do not use sensors
from room controllers as these are not compatible with
the L.B.White SmartBox

™

.

FIG. 12