PHCC Pro Series Pro Series 2400 Battery Backup Sump Pump System User Manual

Page 16

Advertising
background image

TESTING THE FLOAT SWITCH

It is important to manually test the float
switch periodically or after any maintenance.

Unplug the main AC pump when installing or
servicing the backup pump to avoid electric
shock. Failure to do so could cause serious
injury or death. Review the safety
instructions on page 1.

Lift the float up and let go. This will activate
the pump. The control unit will run the pump for
approximately 25 seconds so it can empty all the
water in the sump pit. While the pump is active,
water will come out of the 1/8” hole that was
drilled into the PVC discharge pipe. This is
normal. The hole is needed to prevent an air
lock within the system. DO NOT obstruct the
hole or an air lock may prevent the system from
activating. If there is no water in the pit, the
pump can run dry for this amount of time. The
alarm will sound and the “Pump was activated”
light will go on. After the pump has stopped,
push the GRAY button to silence the alarm. If
the GRAY button is pressed before the pump has
stopped, the alarm will go off temporarily. Wait
for the pump to stop pumping, and then push
the GRAY button on the front of the control unit
to completely silence the alarm. BE SURE TO
PLUG IN THE MAIN AC PUMP WHEN YOU HAVE
COMPLETED THE TEST.

THE REMOTE TERMINAL

The Pro Series 2400 can be connected to a home
security system or other alarm devices to alert
you to a problem or required maintenance.

INSTRUCTIONS FOR CONNECTING THE
REMOTE ALARM

The terminal is located on the back of the
control unit. There are three (3) positions for
wire connections on the terminal: N.C. -
normally closed, N.O. – normally open, and
common.

Check your security system to determine whether
an open (no contact) or closed (making contact)
connection is needed to activate the alarm.

The security system will provide two connection
terminals. You will need to extend wires from
the security system to the Pro Series control
unit. Strip the two wires, ¼” each. Connect
either wire to the common terminal. To secure
the wire into the terminal, insert the exposed
wire into the hole on the back of the terminal
next to the screw marked common. Turn the
screw a few turns to lock-in the wire.

If the security system requires a closing of a
contact to activate the alarm, secure the other
wire in the terminal hole labeled N.O. (normally
open). If the security system requires an
opening of a contact, secure the wire in the
terminal hole labeled N.C. (normally closed).

MAINTENANCE CHECK LIST

Maintenance should be performed 1-2 times per
year

1. Lift the float switch as described at left.

2. Remove all debris from the bottom of the pit.

3. Remove all debris from the water.

4. Remove all debris from the float switch.

5. Fill the pit with water. Make sure the pump

turns on at the intended level.

6. While the pump is running, make sure the

pump is evacuating water at a good pace and
water is coming out of the 1/8” air bleed
hole.

7. Remove the fluid sensor and yellow cap from

the battery and rinse any residue buildup from
the bottom of the battery cap. Replace the
cap and fluid sensor.

8. Check battery fluid levels.

PARTS & SERVICE INFORMATION

You can receive technical support, parts, or
service information by calling Glentronics, Inc.
at 800-991-0466, option #3, or by visiting the
Pro Series website at www.stopflooding.com.
Send your unit to the following address if repairs
are needed:

Glentronics, Inc.

645 Heathrow Drive

Lincolnshire, IL 60069-4205

Page 15

LIFT

FLOAT

!

DANGER

Advertising