Frame Tilt and Oscillation

31200079

7-21

Boom Positioned Above 20° Below 40° With the Service Brake Applied

Fig. 7-14: Circuit Operation Above 20° Below 40° with Service Brake Applied

(Ref. Fig. 7-14) The following describes the rear axle stabilizer circuit logic
when the boom is positioned above 20° below 40° elevation with the
service brake applied.

1. When the boom is above 20° and below 40°, the proximity switch (S2)

is sensing the boom, so the (S2) proximity switch closes. Proximity
switch (S1) is not sensing the boom, so it opens when boom is above
20°.

2. When the proximity switch (S1) is open, the Boom Over 20° relay is not

energized and Solenoid Valve (SV1) is not energized, which restricts
the frame tilt.

3. Applying the service brake locks the rear stabilizer cylinder

hydraulically, which prevents the frame from rotating on the rear axle.

MV0570

VALVE ON VALVE PLATE

REAR AXLE STABILIZER CONTROL

3-WAY SOLENOID VALVE ON

(ENERGIZED)

ON REAR STABILIZER CYLINDER

REAR AXLE STABILIZER VALVE

2-WAY SOLENOID VALVE ON

(ENERGIZED)

SOLENOID VALVE ON

REAR AXLE STABILIZER

CONTROL VALVE

(NOT ENERGIZED)

S2

BOOM ANGLE GREATER THAN 40 - OPEN

BOOM ANGLE LESS THAN 40 - CLOSED

BOOM ANGLE LESS THAN 20 - CLOSED

BOOM ANGLE GREATER THAN 20 - OPEN

S1

OVER 40°

BOOM

86

30

87

87A

85

B

A

SV1

OVER 20°

BOOM

86

30

87

87A

85

RELAY

RELAY

FROM

FUSE PANEL

+12 VOLTS

B

A

SV3

B

A

SV2

NOT ENERGIZED

ENERGIZED

TO RESTRICT

TRANSMISSION

TO 1ST & 2ND

GEARS

TO ENABLE

FOOT SWITCH

AND TO

DISABLE

TRANSMISSION