SECTION 2 - PROCEDURES

3120864

– JLG Lift –

2-77

100HX+10 (110HXER).

1.

Length Indicator Adjustment.

a. Fully retract the boom and place it in the 0 (+3/-

0) degrees horizontal position.

b. With the engine running, check test point 10

(TP10).

c. Set TP1 on the load radius circuit card to 1.8

Volts by adjusting P1.

d. Loosen the Allen screws which anchor the tim-

ing belt pulley (1st generation) or timing gear
(2nd generation) to the shaft of the 5K pot. On
3rd generation sensor boxes, loosen the three
screws holding the pot in place. This enables
the pot/pot shaft to move freely.

e. Turn the ignition switch on. Adjust the 5K pot/pot

shaft until the proper voltage appears at TP2 on
the load radius circuit card and also at the green
wire on the 5K pot. (See Table 2-5 for proper
voltage.)

f. Tighten the Allen screws on the timing belt pul-

ley/timing gear or tighten the three screws, as
applicable.


2.

Boom Angle Sensor Adjustment.

a. With the boom completely retracted and in the 0

(+3/-0) degrees horizontal position, measure
the voltage at TP3 on the load radius circuit card
and at the yellow wire on the boom angle sen-
sor.

b. Adjust the spring-loaded screw on the boom

angle sensor mounting plate (1st generation) or
the trim pot on the boom angle sensor (2nd gen-
eration) until the voltage at TP3 on the load
radius circuit card and the yellow wire on the
boom angle sensor reaches the proper voltage.
For the 3rd generation sensor boxes, loosen the
three screws securing the sensor to the box and
rotate the sensor until the proper voltage read-
ing is obtained, then retighten the screws. (See
Table 2-5 for proper voltage.)




Table 2-5.Card Adjustment - 1st and 2nd Generation

Boom Radius Use Procedure

Model

Length Indicator

Boom Angle Sensor

100HX

2.5 Volts

0.18 Volts

110HX

2.0 Volts

0.20 Volts

100HX+10 (110HXER)

2.5 Volts

0.18 Volts

Table 2-6.Card Adjustment - 3rd Generation

Boom Radius Use Procedure

Adjustment

Location

100HX

Dual Capacity

110HX

Single Capacity

110HX

Dual Capacity

100HX+10

Single Capacity

P1

1.114 Volts

1.155 Volts

1.151 Volts

1.024 Volts

P2

1.585 Volts

2.301 Volts

2.128 Volts

2.263 Volts

P3

1.959 Volts

5.0 Volts

2.548 Volts

5.0 Volts

P4

0.05 Volts

0.05 Volts

0.05 Volts

0.05 Volts

P5

1610 Ohms

1420Ohms

1340 Ohms

1068 Ohms