Operating instructions read heads/actuators cem-a, Setup and functional check, Technical data – EUCHNER CEM-A-xxx User Manual
Page 6: Typical operating distance, Service and inspection

Operating Instructions Read Heads/Actuators CEM-A-...
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]
Subject to technical modifications; no r
esponsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG 114342-04-05/13 (translation of the original operating instructions)
Setup and functional check
Pay attention to the information in the system manual
for the evaluation unit used during setup.
Danger of fatal injuries as a result of faults in
installation and functional check.
f
Before carrying out the functional check,
make sure that there are no persons in the
danger area.
f
Observe the valid accident prevention regula-
tions.
After installation and any fault, the safety function
must be fully checked. Proceed as follows:
f
Switch on operating voltage.
The machine must not start automatically.
f
Close all safety guards.
f
Activate the guard locking.
f
Test the locking force by trying to open the safety
guard. The adhesive force of 500 N or 1,000 N is
attained when U
CM
is applied.
Technical data
Read head
Parameter
Value
Material
- Housing
- Read head CES
- Solenoid
Aluminum
Plastic (PPS)
Galvanized steel
Weight
- CEM-A-LE05...
- CEM-A-LH10...
Approx. 0. kg
Approx. 0.9 kg
Installation position
Any
Degree of protection
according to IEC 60529
IP67
Ambient temperature
-25 ... +50 °C
Operating distance with center
offset m=0
- Assured switch-off distance S
ar
- Switch-on distance typ.
- Switching hysteresis
20 mm
2 mm
0.7 mm
Connection to evaluation unit
(Plug connector X3)
Plug connector M8 (male
socket, 3-pin), suitable for snap-
action and screw terminals
Max. cable length
25 m
External LED connection
(plug connector X2, only
CEM-A-LH10...)
Plug connector M8 (female
socket, 4-pin), suitable for
screw terminals
Max. current consumption of
external LED
500 mA
Solenoid
Locking force (not monitored)
- CEM-A-LE05...
- CEM-A-LH10...
500 N
1,000 N
Adhesive force due to remanence
- CEM-A-LE05K-S2(-EX)
- CEM-A-LE05R-S2
- CEM-A-LH10K-S2
- CEM-A-LH10R-S2
approx. 10 N ± 25 %
approx. 0.5 N
approx. 40 N ± 25 %
approx. 0.7 N
Max. permissible center offset be-
tween solenoid and mating plate
± 2.5 mm
Operating voltage U
B
(plug connector X1)
DC 24 V +10%, -15%
reverse polarity protected
Control voltage U
CM
(plug con-
nector X1)
DC 24 V +10%, -15%, reverse
polarity protected with free-
wheeling diode
Current consumption
Read heads with remanence
- at connection X1.1 (U
CM
)
- CEM-A-LE05K-S2(-EX)
- CEM-A-LH10K-S2
100 mA
225 mA (without external LED)
Current consumption
Read heads without remanence
- at connection X1.1 (U
CM
)
- CEM-A-LE05R-S2(-EX)
- CEM-A-LH10R-S3
- at connection X1.2 (U
B
)
- CEM-A-LE05R-S2(-EX)
- CEM-A-LH10R-S3
15 mA
15 mA (without external LED)
at UCM = 0 V
12 mA
at UCM = 24 V 100 mA
at UCM = 0 V
12 mA
at UCM = 24 V 225 mA
Duty cycle
100 %
Power consumption
- CEM-A-LE05K-S2(-EX)
- CEM-A-LE05R-S2
- CEM-A-LH10K-S3
- CEM-A-LH10R-S3
approx. 2.5 W
approx. 2.8 W
approx. 5.4 W
approx. 5.8 W
Operating voltage connection
(plug connector X1)
Plug connector M8 (male
socket, 4-pin)
For CEM-A-LE05... LED, yellow,
integrated into the plug (see
circuit diagram)
Actuator
Parameter
Value
Material
- Housing
- Read head CES
- Solenoid
Aluminum
Plastic (PPS)
Galvanized steel
Weight
- CEM-A-BE05...
- CEM-A-BH10...
Approx. 0.18 kg
Approx. 0.30 kg
Installation position
Active face opposite CES
read head
Degree of protection
according to IEC 60529
IP67
Ambient temperature
-25 ... +50 °C
Adjustment angle (around point X,
see dimension drawing)
± 4 °
-4
-2
-3
-1
1
3
2
4
0
1
2
3
4
Center offset m [mm]
Distance s [mm]
OFF
ON
Hysteresis
Switch-on
distance
ON
OFF
Hysteresis
Distance s
S
a0
Output state
Switch-off
distance
OFF
Actuator
Read head
s
m
ON
Observe safe switch-off
distance s
ar
= 20 mm on
internal component failure.
Safety outputs are safely
switched off.
Typical operating distance
With evaluation unit CES-A-...B and CES-AZ-...B
Figure 2: Typical operating distance
Service and inspection
No servicing is required, but regular inspection of the
following is necessary to ensure trouble-free long-term
operation:
f
correct switching function
f
secure mounting of components
f
dirt and wear
f
loose cable connections or plug connectors.
If damage or wear is found, the complete
read head and actuator assembly must be
replaced.
Replacement of individual parts or assemblies
is not permitted!
Exclusion of liability under the following
circumstances
f
incorrect use
f
non-compliance with safety regulations
f
installation and electrical connection not per-
formed by authorized personnel.
f
failure to perform functional checks.