2.4 Replacing a defective Slave (with teach-in of actuator)
All safety slaves with necessity for teach-in of an actuator like CES and CET can be replaced
without using a PC with ASiMon according to this method.
1. Disconnect the defective slave from AS-Interface Bus
2. Connect new slave with address 0. Close locking if necessary.
– The master addresses this slave automatically
3. Teach-in of actuator according to operation manual
4. Dissconnect new slave from AS-Interface Bus
5. Press the service button on the monitor
– The monitor stores which slave address is missing
6. Connect new slave AND bring it into a safe state
7. Press the service button on the monitor
– The monitor has a check on the safety function of the new slave