Flint & Walling Centrifugal Packages - end suction centrifugal pumps User Manual

Page 4

Advertising
background image

4

95 North Oak Street • Kendallville, IN 46755

Copyright 2011. All Rights Reserved.

SINGLE PHASE

Distance From Motor

To Fuse Box Meter,

or Electrical Outlet

Recommended Copper Wire Size

1HP

1-1/2 HP

2 HP

3 HP

5 HP

100 ft.

115V

230V

10
14

8

12

8

10

*
8

-

6

150 ft.

115V

230V

6

12

6

12

4

10

*
8

4

200 ft.

115V

230V

6

12

6

10

4
8

*
6

-

4

300 ft.

115V

230V

*

12

*
6

*
6

*
4

-

2

500 ft.

115V

230V

*

10

*
4

*
4

*
2

-

0

(*) Not economical to run at 115V, use 230V.
Figure 3

THREE PHASE

Distance From

Motor To Fuse

Box Meter, or

Electrical Outlet

Recommended Copper Wire Size

1HP

1-1/2

HP

2 HP 3 HP 5 HP

7-1/2

HP

100 ft.

230V
460V

14
14

12
12

12
12

12
12

10
12

8

12

150 ft.

230V
460V

14
14

12
12

12
12

10
12

8

12

6

12

200 ft.

230V
460V

14
14

12
12

12
12

10
12

8

12

6

12

300 ft.

230V
460V

12
14

12
12

10
12

8

12

6

10

4

10

500 ft.

230V
460V

10
14

10
12

8

12

6

10

4
8

2
8

Figure 4

MOTOR PROTECTION

WARNING: Never examine, make wiring changes

or touch the motor before disconnecting the main

electrical supply switch.
1.

Motors may or may not have built-in thermal
overload protection depending upon the
horsepower size, phase, type and motor
manufacturer. Refer to the motor nameplate for
overload protection information. It is recommended
that a properly sized magnetic or manual starter
(both with properly sized heaters) be used with all
motors. Install starters following instructions of the
starter manufacturer. See Figure 5 & 6 for magnetic
starter wiring diagram.

2. All motors (single and three phase) should be

equipped with a correctly fused disconnect switch
to provide protection. Consult Local or National
Electrical Codes for proper fuse protection based on
motor nameplate.

3. Undersize wiring can cause motor failure (low

voltage), frequent cut-out of motor overload
protector, television interference and even fire.
Make certain the wiring is adequately sized (Figure
3 & 4), well insulated and connected to a separate
circuit outside the building in case of fire.

Figure 5

Warning: Connect

motor leads

momentarily for

correct rotation

Motor

Pressure
Switch

Magnetic Starter Wiring
Diagram - Single Phase

Fused
Disconnect
Switch

Lightning
Arrestors

#10 Or Heavier Copper Ground Wire,
Connect To 8 ft. Ground Rod Or Well Casing

L1

L2

3

2

1

V

M

W

T1

T2

T3

X2

IL0102

Figure 6

Pressure Switch

Magnetic Starter Wiring
Diagram - Three Phase

Fused Disconnect
Switch

Lightning
Arrestors

#10 Or Heavier Copper Ground Wire,
Connect To 8 ft. Ground Rod Or Well Casing

Motor

1

W

V

T3

X2

T2

T2

T1

M

L3

L2

L1

3

2

OPERATION
PRIOR TO STARTING
1. Before the pump is started initially, make the

following inspections:

• Check Rotation - Be sure that the pump operates in

the direction indicated by the arrow on the pump
casing, as serious damage can result if the pump
is operated with incorrect rotation. Rotation is
always counterclockwise facing the pump suction.
Operating the pump in reverse rotation may cause
extensive damage.

• Check all connections to motor and starting device

with wiring diagram. Check voltage, phase and
frequency on motor nameplate with line circuit.

ALL PUMPS WITH 3 PHASE MOTORS MUST BE

INSTALLED WITH A MAGNETIC STARTER WHICH

PROVIDES 3-LEG PROTECTION FOR MOTOR.

FAILURE TO USE CORRECT STARTER WILL VOID THE

WARRANTY.

PRIMING
1. Before starting any centrifugal pump it is absolutely

necessary that both the casing and suction pipe be