1. Disconnect all three drop cables from the control

box. For temporary identification, tie a numbered

tag to each cable (1, 2, 3).

2. Using an ohmmeter, check the resistance

between cables as follows:

Unknown Value

Known Value

Cable 1 to Cable 2

Cable 1 to Cable 3

Cable 2 to Cable 3

Lowest - Black to Yellow

Intermed. - Red to Yellow

Highest - Black to Red

NOTE: The “yellow” cable is that giving lowest and

intermediate readings and the “red” cables gives

highest and intermediate readings.

Example:

• 1 to 2 gives 7 ohms (highest reading)

• 1 to 3 gives 5 ohms (intermediate reading)

• 2 to 3 gives 2 ohms (lowest reading)

• Cable 3 gave both intermediate and lowest

reading

• Cable 3 is the yellow cable

• Cable 1 gave both highest and intermediate

readings

• Cable 1 is the red cable

• Cable 2 is the black cable

The actual ohm values are not important. The

method works regardless of the actual ohm readings;

what matters is which reading is highest, which

intermediate, and which lowest.

THREE PHASE POWER UNBALANCE

1. A full three phase supply is recommended for all

three phase motors, consisting of three individual

transformers or one three phase transformer.

So-called “open” delta or wye connections using

only two transformers can be used, but are more

likely to cause problems from current unbalance.

Transformer Capacity Required for

Submersible Motors

Motor

HP

Total

Effective

KVA

Required

Smallest KVA Rating — Each

Transformer

Open WYE or

DELTA

2 Transformers

Closed WYE or

DELTA

3 Transformers

1-1/2

2

3

5

7-1/2

10

15

20

25

30

40

50

60

75

100

3

4

5

7.5

10

15

20

25

30

40

50

60

75

90

120

2

2

3

5

7.5

10

15

15

20

25

30

35

40

50

65

1

1.5

2

3

5

5

7.5

10

10

15

20

20

25

30

40

2. Transformer ratings should be no smaller than

listed in the table for supply power to the motor

alone. Open Wye or Delta systems often

suffer from line unbalance, which can cause

poor motor performance, nuisance overload

tripping, or premature motor failure. For the

best performance current unbalance should not

exceed 5 percent. If the unbalance cannot be

corrected by rolling leads, contact the power

company.

INSULATION RESISTANCE

Unbalance Formula

Percent

Current = Max difference from average x 100

Unbalance average

Example:

Currents are 80, 79, 84 amps (Lines 1-2 & 3)

Avg. Currents = 80 + 79 + 84 = 81

3

Percent

Current

Unbalance

84 - 81 x 100 = 3.7%

81

IL0104

Figure 13

Open Delta

Full Three Phase

Insulation resistance tests indicate the value of the

motor, cable, and splice insulation system by

measuring resistance in ohms between motor leads

and ground. Low readings indicate a breakdown

somewhere in the insulation system.

1. Set ohmmeter to RX100K or highest scale. (For

best results use a megohmmeter).

2. Short meter leads together and adjust indicator to

zero.

3. Be sure power is turned off!

4. Connect one meter lead to a motor lead and the

other meter lead to ground.

a. If motor is out of water, measure from lead to

motor frame.

b. If motor is installed in water, ground reference

should be metal well casing (if submerged),