MAGNETIC STARTERS FOR 3 WIRE FRANKLIN MOTORS

Overload Protection • 4”, 6” & 8” Submersible Motors – 60 Cycle – 3 Phase

MOTOR

SIEMENS/FURNAS CLASS 16

STARTER

HEATER

HP

VOLTS

F&W PART NO.

Size Full Load AMPS

F&W PART NO.

SIZE

F&W PART NO.

4” FRANKLIN SUBMERSIBLE MOTORS – 60 HZ – 3 PHASE

1 1/2

200

137457

25

139324

K43

130274

230

137458

K41

130272

460

137460

139325

K29

134872

2

200

137461

25

139324

K50

133010

230

137462

K43

130274

460

137464

139325

K33

130275

3

200

137465

25

139324

K54

130282

230

137466

K52

130276

460

137468

139325

K37

130277

5

200

137469

25

139324

K61

133016

230

137470

K61

133016

460

137472

139325

K49

130280

7 1/2

200

137473

25

139324

K68

130288

230

137474

K67

133020

460

137476

139325

K55

133013

6” & 8” FRANKLIN SUBMERSIBLE MOTORS – 60 HZ – 3 PHASE

5

200

133492

25

139324

K61

133016

230

133493

K61

460

133494

25

139325

K49

130280

7 1/2

200

130646

30

139326

K68

130288

230

126552

25

139324

K67

133020

460

128876

25

139325

K55

133013

10

200

130647

40

139327

K72

131724

230

126554

K70

133018

460

128875

25

139325

K58

130279

15

200

130648

60

139328

K76

130691

230

126555

50

139329

K75

130293

460

128884

25

139325

K64

130281

20

200

130649

75

139330

K78

130289

230

128754

K77

130287

460

128888

40

139331

K69

135548

25

200

130650

120

139332

K86

131725

230

128755

90

139333

K83

133021

460

128890

40

139331

K72

131724

30

230

128964

120

139332

K87

135549

460

128965

50

139334

K74

130285

40

460

021003

75

139335

K77

130287

50

460

021004

90

139336

K83

133021

60

460

023029

91

023032

K87

135549

75*

460

023030

107

023032

K89

023034

100*

460

023031

142

023033

K94

023035

*Denotes 8” motor
CAUTION: WARRANTY ON THREE PHASE SUBMERSIBLE MOTORS IS VOID UNLESS PROPER
QUICK TRIP PROTECTORS ARE USED ON ALL 3 LEAD WIRES.
The characteristics of submersible motors are different from standard motors and special overload protection is required. If the motor is
stalled, the overload protector must trip within approximately 10 seconds to protect the motor windings. In the three phase submersible
motors, the installer must provide the SPECIAL EXTRA QUICK TRIP PORTECTORS AS TABULATED. The heaters given are for ambient
compensated starter boxes; if they are not used, nuisance tripping (over protection) may be experienced at high temperatures and no
protection will exist at low temperatures.
Overload protectors (heaters) for motors of “200-230 volt” ratings should be selected for each installation based on the line voltage
measured at the control panel.