Installation continued – Garland XG36CE BE/FR MASTER SERIES GAS XPRESS GRILL User Manual

Page 9

Advertising
background image

Part # 4517129 Rev.1 (03/10/10)

Page 9

Additional Burner Ignition Verification:

1. Drop the front control panel so that the heat shield is

visible.

2. Turn the grill ON and press the ON/OFF switch on the

control to heat the grill in Standby Mode.

3. Rotate the round shutter to expose the burner sight glass.

4. When the grill attempts to ignite the burners, look

through the sight glass to verify ignition.

The burner should ignite and the flame should appear blue

with no orange tipping. If the burner flame cannot be seen,

inspect ignition and gas system for possible problems.

Burner Air Adjustment:

Once burner ignition is verified by looking through the sight

glass, burner air adjustment may be required. Adjust the

burner air as follows:

1. Loosen the lock nut on the blower motor shutter.

2. The blower shutter can be rotated to allow more or less

air into the burners.

3. Adjust the shutter until the burner flame is blue with no

orange tipping.

4. Tighten the lock nut.

INSTALLATION continued

NOTE: Burner air shutters should only be adjusted by factory

authorised service personnel.

Ventilation and Clearance:

One of the most important considerations of efficient grill

operation is proper ventilation and air supply. Insure the

grill is installed so the products of combustion are removed

efficiently and the ventilation system does not produce

drafts that interfere with proper burner operation.

Proper operation of exhaust fans (speed, rotation and

adjustment) is essential. In addition to the exhaust system

the make-up air system, (HVAC), for the kitchen is the

air supply for the combustion air for the burners. Proper

incoming air is essential for all gas operated equipment. Poor

incoming make-up will cause inefficient burner operation,

delayed ignition and possible burner failure.

Any ventilation system will break down if improperly

maintained. The duct system, hood, and the filters must be

cleaned on a regular basis and kept grease free.

The room containing the grill is required to have a

permanent air vent. The minimum effective area of the vent

shall be 4.5 cm² per kW. Air vents shall be of such a size to

compensate for the effects of any extract fan in the premises.

NOTE: Parts which have been protected by the

manufacturer and agent, are not to be adjusted by the

installer or the user.

Advertising
This manual is related to the following products: