21. ANA TEST

View the control level for each of the analog inputs.

The analog voltage level for the 4 analog inputs can be tested and viewed as a

percentage or hexadecimal value. The level displayed is proportional to the 0-10VDC

analog input where 5VDC is 50%.

Press EXECUTE to enter the menu and activate analog test mode.

AI>01=00

Displays the active analog input (AI>01) and the level (00).

AI>04=00

Press MENU (

) to select the desired analog input to test.

AI>04=FL

Displays the analog input level from off (00) to full-on (FL).

Press ESCAPE or RESET to exit the menu.

22. ANA FLTR

Apply a noise filter on the analog inputs of up to 1 Volt.

High frequency noise can sometimes be induced into the analog input lines. The

analog filter is set in 1% increments where each percent (%) represents 0.1 Volts for

a maximum filter level of 1 Volt, or 10%. For example, when the analog filter level is

set at 5% (LEV:05%) all analog input levels at or below 0.5 Volts is ignored or filtered out.

LEV:00%

Displays the filter level (00%) in percent.

LEV:00%<

Press EXECUTE to enter the menu and adjust the analog filter level.

LEV:10%<

Press MENU (

) to select the desired filter level.

Press ESCAPE to exit the menu and save the desired analog filter level.

Press RESET to exit the menu without saving.

The menu will automatically timeout after 5 minutes of inactivity and save.

23. ANA BLOC

Enable or disable the analog inputs when DMX is being received.

When analog blocking (ANA BLOC) is enabled the analog inputs will be ignored when

DMX is online. When analog blocking is disabled the analog inputs will be merged/

combined with the DMX inputs and functions in a highest-takes-precedence (HTP)

mode of operation.

ENABLED

Press EXECUTE to toggle analog blocking from ENABLED to DISABLED.

DISABLED

Press EXECUTE to toggle analog blocking from DISABLED to ENABLED.

Any change in the configuration is automatically saved.

24. STANDBY

Enable or disable the power savings standby mode.

When standby mode is enabled the microcontroller goes to sleep within 5 seconds

of inactivity on the control inputs. The microcontroller wakes up again when a

programming switch is pressed or when control is sensed on the control inputs. Note

that there is a delay of 150 milliseconds for the microcontroller to wake up and restart

normal run mode.

ENABLED

Press EXECUTE to toggle standby mode from ENABLED to DISABLED.

DISABLED

Press EXECUTE to toggle standby mode from DISABLED to ENABLED.

Any change in the configuration is automatically saved.

25. TEST INC

Set the test increment units to percent or hexadecimal.

The levels for the dimmer test (DIM TEST) and analog test (ANA TEST) features can

be displayed as a percentage or hexadecimal value.

PERCENT

Press EXECUTE to toggle test increments from PERCENT to HEX VAL.

HEX VAL

Press EXECUTE to toggle test increments from HEX VAL to PERCENT.

Any change in the configuration is automatically saved.