3 subordinate control loop, 4 load voltage adjustment, Subordinate control loop – JUMO 709050 IPC IGBT Power Converter IPC 70/100A Operating Manual User Manual

Page 33: Load voltage adjustment, 5 settings

Advertising
background image

02.08 [IGBT Power Converter 70/100A]

33

5 Settings

5.3 Subordinate control loop

Subordinate control loops are primarily used to eliminate or compensate for
external disturbances, such as fluctuations in the supply voltage and
alterations in resistance that have a negative effect on the operation of the
control loop.

Factory setting

A subordinate U

2

control loop is factory set,

however, also the P or I

2

control loop is possible.

k

factory setting

5.4 Load voltage adjustment

Switch S101-7 can be used to adjust the load voltage.
If the max. load voltage required is less than 75% of the
load voltage U

L Nom

as per type code, then S 101-7 must be opened.

If the maximum required load voltage is 75% or more of the nominal load
voltage U

L Nom

as per type code, then S 101-7 must be closed.

Factory setting

S101-7 is closed.

Control
type

Internal switch S101

Application

S1

S2

S3

U

2

1

0

0

- positive TC, Molybdenum Disilicid

- R

≈ constant

- brightness controls

P

0

1

0

- general application,
required for SIC loads and
automatic compensation for ageing.

I

2

0

0

1

- negative TC