7 troubleshooting – JUMO 709050 IPC IGBT Power Converter IPC 70/100A Operating Manual User Manual
Page 50

50
[IGBT Power Converter 70/100A] 02.08
7 Troubleshooting
IPC does not produce
full power, although
setpoint is set to 100%
- Switch positions for control input S 101/8
and 9 or S104 set incorrectly
- Control input (max. Power adjust) is not
turned clockwise to the stop
h Check adjustment
„Control input
adjustment (max.
Power adjust)“
- Current limiting active (when the red
„current limit“ LED is lit)
h Turn the „max. current adjust“ trimmer
clockwise
„Setting the current
limit (max. current
adjust)“
- Resistance limiting (R-control) active
h Check switch S 101/10
switches S101,
S103, S104, S105,
S106 and X106“
h Check switch S 103
h Check switch S 101/7
IPC is producing power,
although no setpoint
value is set
- Check switches S 101/ 8 and 9 or S104
for control input
- Base load setting (max. Power adjust) is
not turned counter-clockwise to the stop
h Check switch S 101/11
the base load (min.
Power adjust)“
What is happening?
Cause / Remedy
Information