English, Symbols used on lcd, Electrical specifications – Klein Tools CL3000 User Manual

Page 3

Advertising
background image

ENGLISH

Do not measure resistance

on a live circuit.

Ω

< 40MΩ

Resistance Features:

HOLD RANGE

4.

Frequency / Duty Cycle

Features:

HOLD

• Input Voltage should be between 1V-10V RMS for listed accuracy.

5. Resistance / Diode / Continuity

Display shows:
• Forward voltage drop if forward biased.
• “O.L.” if reverse biased.

Diode Features:

HOLD

• Display shows resistance.
• Buzzer sounds if less than 30

Ω

Continuity Features:

HOLD

6. Capacitance:

< 40µF

Features:

REL

HOLD

• ?

Safely discharge capacitor before measurement.

• Wait up to 60 seconds for reading.

PRESS

TO SELECT

Diode

Resistance

Continuity

AUTO

V

DC

PRESS

%

AUTO

V

DC

AUTO

V

DC

AUTO

V

DC

AUTO

V

DC

SYMBOLS USED ON LCD

~

AC Measurement

DC Measurement

-

Negative DC Value

REL

Relative Mode

Low Battery

H

Hold Active

AUTO

Auto Range Active

V

Voltage Measurement

%

Duty Cycle Mode

Frequency Mode

A

Current in Amps

Ω

Resistance in Ohms

Diode Test

Continuity Test

F

Capacitance in Farads

n

Nano 10

-9

µ

Micro 10

-6

m

Milli 10

-3

k

Kilo 10

3

M

Mega 10

6

ELECTRICAL SPECIFICATIONS

DC Voltage Measurement

Range

Resolution

Accuracy

4V

0.001V

± (0.7% + 2 digits)

40V

0.01V

400V

0.1V

1000V

1V

± (0.8% + 3 digits)

Overload Protection:

1000V DC / 750V AC RMS

Input Impedance:

10M

Ω

AC Voltage Measurement

Range

Resolution

Accuracy

4V

0.001V

± (0.8% + 5 digits)

40V

0.01V

400V

0.1V

750V

1V

± (1.0% + 10 digits)

Overload Protection:

1000V DC / 750V AC RMS

Frequency:

50 to 60Hz

Input Impedance:

10M

Ω

Response:

Averaging

AC Current Measurement

Range

Resolution

Accuracy

200A

0.1A

± (3.0% + 3 digits)

Overload Protection:

240A for 60 sec.

Frequency Response:

50 to 400Hz

Response:

Averaging

Advertising