Settings, Settings 6 – Lenze 8400 motec Mounting Instructions User Manual

Page 52

Advertising
background image

Settings

6

l

52

EDK84DGDVBxxx4 DE/EN/FR/ES/IT 5.3

6

Settings

For initial commissioning, settings can be made via DIP switch and
potentiometer. The settings must be made before mounting the drive unit since
the setting elements cannot be accessed from the outside.

(

Stop!

Automatic motor start

In "Local mode" The auto−start option "Inhibit at power−on" is not
set. When the mains is connected, the motor starts if the controller
enable RFR is bridged or set.

("Local mode" => DIP1/1 = ON and DIP2/5−7 = OFF)
Possible consequences:

ƒ

Danger or damages through unexpected motor start.

Protective measures:

ƒ

Decouple the motor from the drive train during commissioning
phase.

ƒ

Replace the factory−set bridge at RFR by an NO contact.

ƒ

Do not set controller enable.

Advertising