Settings

Setting with the diagnosis terminal (keypad)

Measures when drive is used in IT systems

6

l

59

EDK84DGDVBxxx4 DE/EN/FR/ES/IT 5.3

6.3

Measures when drive is used in IT systems

If the drive is mounted within an IT system, internal filters must be separated
from the PE conductor.
How to proceed:
1. If the controller has already been mounted: switch off mains voltage!
2. Make IT screw accessible.

Devices up to 3 kW: unscrew small cap on the top.

Devices from 4 kW: remove small cover on the top.

3. Unscrew and remove the screw(s).
4. Screw the cap on or fit the cover.

IT system

0.37 ... 3 kW

E84DG046