Electrical installation, Block diagram, Connection terminals – Lenze EZVxxxx-000 Power supply unit AC 230V 5A-20A User Manual

Page 20: 2electrical installation

Advertising
background image

2

Electrical installation

Block diagram

EDKZV1200 DE/EN/FR/ES/IT 1.0

20

l

H1_E_INST−funktion

2

Electrical installation

Block diagram

L

N

PE

+

+

-

-

DC OK

13

14

DC 22.5

… 28.5 V

DC 24.0 V /

max. 40 mA

AC 85

… 264 V

1

ezvxx00−000_07

Connection terminals

ƒ Power supply unit AC 230 V, DC 24 V, 5 A
ƒ Power supply unit AC 230 V, DC 24 V, 10 A

Input terminals

Output terminals

Rigid terminal

0.2 ... 2.5 mm

2

(AWG 24 ... 12)

0.2 ... 2.5 mm

2

(AWG 24 ... 12)

Flexible terminal with wire end
ferrule with plastic collar

0.2 ... 2.5 mm

2

(AWG 24 ... 12)

0.2 ... 2.5 mm

2

(AWG 24 ... 12)

Stripping length

7 mm

7 mm

Tightening torque

0.5 ... 0.6 Nm
(4.4 ... 5.3 lb−in)

0.5 ... 0.6 Nm
(4.4 ... 5.3 lb−in)

ƒ Power supply unit AC 230 V, DC 24 V, 20 A

Input terminals

Output terminals

Rigid terminal

0.2 ... 6.0 mm

2

(AWG 24 ... 10)

0.5 ... 16.0 mm

2

(AWG 20 ... 6)

Flexible terminal with wire end
ferrule with plastic collar

0.2 ... 4.0 mm

2

(AWG 24 ... 10)

0.5 ... 10.0 mm

2

(AWG 20 ... 6)

Stripping length

7 mm

10 mm

Tightening torque

0.5 ... 0.6 Nm
(4.4 ... 5.3 lb−in)

1.2 ... 1.5 Nm
(10.6 ... 13.3 lb−in)

Advertising