Wiring the input terminals, Electrical installation, Danger – Lenze EZVxxxx-000 Power supply unit AC 230V 5A-20A User Manual
Page 21
Electrical installation
Wiring the input terminals
EDKZV1200 DE/EN/FR/ES/IT 1.0
21
l
H1_E_INST−funktion
Wiring the input terminals
The device can either be connected to single−phase AC systems or to two phase conductors
of three−phase systems (TN, TT or IT system to VDE 0100 T 300/IEC 364−3) with rated
voltages of AC 100 ... 240 V.
{
Danger!
For the operation on two phase conductors of a three−phase system it is vital
to provide an all−pole disconnecting device for the protection of persons.
L
N PE
L
N PE
L
5
5
5
5
5
5
5
1/N/PE AC 100 … 240 V
45 … 65 Hz
3/N/PE AC 100 … 240 V
45 … 65 Hz
1/PEN AC 100 … 240 V
45 … 65 Hz
3/PEN AC 100 … 240 V
45 … 65 Hz
1/N AC 100 … 240 V
45 … 65 Hz
3/N AC 100 … 240 V
45 … 65 Hz
3 AC 100 … 240 V
45 … 65 Hz
L
L1
L1
L1
L1
L2
L2
L2
L2
L3
L3
L3
L3
L
N
N
N
PEN
N
PE
PEN
PE
L
N PE
L
N PE
L
N PE
L
N PE
L
N PE
TN-S
TN-S
TN-C
TN-C
TT
TT
IT
ezvxx00−000_06
5
Circuit−breaker 6 A/ 10 A/ 16 A (characteristic B or C)