Technical data
EDKZV1200 DE/EN/FR/ES/IT 1.0
25
l
H1_Daten−−−−(DUMMYSEITEVOR)−−−
General electrical data
Power supply unit AC 230 V, DC 24 V
5 A
10 A
20 A
Degree of protection
IP 20
Class of protection
I (with PE connection)
Leakage current to PE
< 3.5 mA
MTBF
to IEC 1709 (SN 29 500)
> 500 000 h
Max. power loss
(idle state/ rated load)
2 W / 14 W
2 W / 24 W
3 W / 44 W
Efficiency
at AC 230 V and rated values
> 89 %
> 91 %
> 92 %
Input data
Power supply unit AC 230 V, DC 24 V
5 A
10 A
20 A
Turn−on time
< 1 s after applying the mains voltage
Transient surge voltage protection
varistor
Mains voltage range
AC 85 V − 0 % ... 264 V + 0 %, 45 Hz − 0 % ... 65 Hz + 0 %
Current
consumption
AC 120 V 1.6 A
2.3 A
4.8 A
AC 230 V 0.8 A
1.2 A
2.3 A
Starting current limitation /
I
2
t (+25 °C)
typ. < 15 A /
< 2.5 A
2
s
typ. < 15 A /
< 1.5 A
2
s
typ. < 15 A /
< 3.2 A
2
s
Mains buffering at
rated load
AC 120 V typ. > 20 ms
typ. > 50 ms
typ. > 30 ms
AC 230 V typ. > 120 ms
−
−
Recommended back−up fuse
circuit−breaker
(characteristic B or C)
6 A / 10 A / 16 A