Function monitoring, Electrical installation – Lenze EZVxxxx-000 Power supply unit AC 230V 5A-20A User Manual

Page 23

Advertising
background image

Electrical installation

Function monitoring

2

EDKZV1200 DE/EN/FR/ES/IT 1.0

23

l

H1_E_INST−funktion

Function monitoring

The LED, the active "DC OK" switching output and a potential−free contact provide the
function monitoring.

LED

"DC OK"
switching
output

Potential−
free contact

Output voltage

Info

AN

V = 24 V

closed

V

output

> 0.9

U

input

Device is in operation,

l

the output voltage V

output

is higher than 90 % of the
set voltage V

input

l

the output current is in the
permissible range

BLINKING

U = 0 V

open

V

output

< 0.9

V

input

Device is in operation but

l

error at the load

l

current consumption is
higher than I

BOOST

l

output is short−circuited

OFF

U = 0 V

open

V

output

= 0

Device is out of service because

l

no mains voltage is applied

l

the circuit−breaker is
activated

l

the device is defect

)

Note!

The device is defective and needs to be replaced if the mains voltage is applied,
a short circuit can be excluded and an output voltage of V

output

= 0 V is

measured.

Advertising