Lenze E82ZWBRE User Manual

Page 30

Advertising
background image

2

Safety instructions

Safety instructions for the installation according to UL

EDK82ZWBRE DE/EN/FR 6.0

30

l

H1sic_EN−UR_WARN_COA_E82ZWBRx

Safety instructions for the installation according to UL

O

Warnings!

Conditions of Acceptability:

ƒ

These devices should be used within their marked Recognized ratings.

ƒ

These devices should be mounted within a suitable ultimate enclosure
with proper spacings being maintained.

ƒ

Maximum surrounding air temperature 60 °C.

ƒ

Use 75°C copper wires only, min. wire size 20 AWG.

ƒ

These devices are intended for use with Power Conversion Equipment (e.g
for use with of Lenze Drives as registered in File E132659 Vol.11, Sec. 1
(series E82MV)).