Electrical installation, 24 v supply from dc-bus connection, Fuse – Lenze EZVxx00−001 Power supply unit AC 400V 5A-20A User Manual

Page 23: Permissible dc input voltage

Advertising
background image

Electrical installation

24 V supply from DC−bus connection

2

EDKZV1200 DE/EN/FR/ES/IT 1.0

23

l

H1_E_INST−funktion

3

Electrical installation

24 V supply from DC−bus connection

L1

L2

L3

PE

+

+

-

-

22.5 V DC

28.5 V DC

U

= 450 V DC … 800 V DC

G

7

EZVxx00-001

U

G

ezv1201_07−dc

Fuse

7

An additional external fuse must be connected between the power supply unit and the
controllers operated in the system (see illustration

7).

The size of the fuse is
ƒ 6 A for power supply unit AC 400 V, DC 24 V, 5 A
ƒ 10 A for power supply unit AC 400 V, DC 24 V, 10 A
ƒ 16 A for power supply unit AC 400 V, DC 24 V, 20 A

Permissible DC input voltage

The DC input voltage of the power supply unit corresponds to the DC−bus voltage V

G

of the

DC−bus connection.

The DC−bus voltage must be within the following value range:
ƒ V

G

= 450 V DC ... 800 V DC

Advertising