Function monitoring, 2electrical installation – Lenze EZVxx00−001 Power supply unit AC 400V 5A-20A User Manual

Page 24

Advertising
background image

2

Electrical installation

Function monitoring

EDKZV1200 DE/EN/FR/ES/IT 1.0

24

l

H1_E_INST−funktion

Function monitoring

The LED, the active "DC OK" switching output and a potential−free contact provide the
function monitoring.

LED

"DC OK"
switching
output

Potential−
free contact

Output voltage

Info

AN

U = 24 V

closed

V

output

> 0.9 V

input

Device is in operation,

l

the output voltage
V

output

is higher than 90

% of the set voltage V

input

l

the output current is in
the permissible range

BLINKING

U = 0 V

open

V

output

< 0.9 V

input

Device is in operation but

l

error at the load

l

current consumption is
higher than I

BOOST

l

output is short−circuited

OFF

U = 0 V

open

V

output

= 0

Device is out of service
because

l

no mains voltage is
applied

l

the circuit−breaker is
activated

l

the device is defect