background image

Technical data

4

EDKZV1200 DE/EN/FR/ES/IT 1.0

25

l

H1_Daten−−−−(DUMMYSEITEVOR)−−−

4

Technical data

General data /
operating conditions

Power supply unit AC400 V, DC 24 V

5 A

10 A

20 A

Conformity

CE

l

Low−Voltage Directive (2006/95/EG)

l

EMC Directive (2004/108/EG)

Approval

UL508 Industrial Control equipment (file no. E123528)

Vibration resistance

to IEC 68−2−27

up to 30 g

Climatic conditions

to EN 60 721

Class 3K3

Degree of pollution

to EN 50 178

2

Permissible temperature ranges

l

Storage: −40 °C ... +85 °C

l

Operation: −25 °C ... +70 °C,
the output current must be reduced by 2.5 %/°C above a
temperature of +60 °C

Humidity

< 95 % , at +25 °C, no condensation

Free space

> 50 mm, above / below

Dimensions (B ×

H × T)

73 Ч 130 Ч 125
mm

85 Ч 130 Ч 125
mm

160 Ч 130 Ч 125
mm

Weight

0.95 kg

1.1 kg

1.93 kg

General electrical data

Power supply unit AC 400 V, DC 24 V

5 A

10 A

20 A

Degree of protection

IP 20

Class of protection

I (with PE connection)

Leakage current to PE

< 3.5 mA

MTBF

to IEC 1709 (SN 29 500)

> 500 000 h

Max. power loss

(idle state/ rated load)

3 W / 17 W

4 W / 28 W

7 W / 47 W

Efficiency

at AC 230 V and rated values

> 88 %

> 90 %

> 91 %

Advertising