Technical data
Rated data
l
46
EDK94AZMP45 DE/EN/FR/ES/IT 7.0
4.2
Rated data
Mains
Voltage
Voltage range
Frequency range
U
Lrated
[V]
U
Lrated
[V]
f [Hz]
3/PE AC
230
180 − 0 % ... 264 + 0 %
45 − 0 % ... 65 + 0 %
3/PE AC
400
320 − 0 % ... 440 + 0 %
45 − 0 % ... 65 + 0 %
3/PE AC
500
400 − 0 % ... 550 + 0 %
45 − 0 % ... 65 + 0 %
Voltage
Freq.
Current [A]
Current [A]
Number
of phases
[V]
[Hz]
max. +45° C
max. +55° C
E94AZMP0824
230/400/500
50/60
82/82/82
61/61/61
3
E94AZMP2004
230/400/500
50/60
200/200/200
150/150/150
3
E94AZMP0824
2)
400/500
50/60
49/49
30.6/30.6
3
Temperature in the control cabinet
2)
For i700 mounting: mains connection at the bottom, output at the top
Power loss
Inductance
Voltage drop
P
loss
[W]
L [mH]
DU [V]
E94AZMP0824
200
0.25
6.4
E94AZMP2004
350
0.10
6.3
Thermal contact
Design
max. switching voltage
max. switching current
U
Th
[V AC]
I
Th
[A]
E94AZMP0824
NC contact, 150 °C
250
2.5
E94AZMP2004
Fan
Voltage
Current
[V DC]
[A]
E94AZMP0824
24
0.3
E94AZMP2004