Electrical installation

Mounting steps

6

l

63

EDK94AZMP45 DE/EN/FR/ES/IT 7.0

Use with 9400
How to connect the filter:
1. Connect filter output cables (X302/L1’, L2’, L3’, PE’) to power supply

module.

2. Remove cover

0.

3. Use ring cable lugs to bolt mains cables onto threaded bolts X301/L1, L2,

L3.

Observe tightening torque! (

60)

4. Use ring cable lug to bolt mains−side PE conductor onto threaded bolt

X301/PE.

Observe tightening torque! (

60)

PE connection must comply with EN 61800−5−1 .

5. Use cable binders to fix all mains−side cables at strain relief sheet

1.

6. Assemble cover

0.

The filter must not be commissioned without cover

0!

7. Connect the thermal contact cable to T1 and T2 terminals.

Integrate the thermal contact into the system monitoring in order that
the mains supply will be switched off in case of filter overheating.

8. Connect voltage supply for internal fan to terminal X11.

Use with i700
How to connect the filter:
1. Connect filter output cables (X302/L1’, L2’, L3’, PE’) to power supply

module.

Cable ends (cable lugs) may be removed.

Cable lengths may be shortened, if required.

Do not use wire end ferrules for connecting filter output cables to the
i700 supply terminal.

2. Remove cover

0.

3. Use ring cable lugs to bolt mains cables onto threaded bolts X301/L1, L2,

L3.

Observe tightening torque! (

60)

4. Use ring cable lug to bolt mains side PE conductor onto threaded bolt

X301/PE.

Observe tightening torque! (

60)

PE connection must comply with EN 61800−5−1.

5. Use cabke binders to fix all mains side cables on strain relief sheet

1.

6. Assemble cover

0.

The filter must not be commissioned without cover

0!