Wiring the device

Important notes

5

l

62

EDK94SH104 DE/EN/FR/ES/IT 5.1

IT system

(

Stop!

Overvoltage on components:
In case of an earth fault in IT systems, incompatible overvoltages may occur in
the plant.
Possible consequences:
Destruction of the device.
Protective measures:
When using the devices in IT systems, separate the internal connection of
filters to the protective earth. For this purpose carry out the device−specific
measure as described.

Proceed as follows to disconnect the internal connection between the filters and PE:

1. Find the screw over terminals X100 (+UG/−UG) in the position "TT−TN" (

¶ Fig. 5−1).

2. Unscrew the screw and screw it in again at position "IT".

– Tightening torque: 3.4 Nm (30 lb−in)

94GG67IT01

Fig. 5−1

3. Find the metal strap on the left of the device (

¶ Fig. 5−2).

4. Unbolt the screws to remove the metal strap.

5. Unbolt the screw at position "IT" and insert the metal strap.

6. Tighten all screws.

– Tightening torque: 3.4 Nm (30 lb−in)

Device size 6

Device size 7

94GG67IT62

94GG67IT72

Fig. 5−2

After this, the device is suitable for operation in IT systems.