Module status displays, 8diagnostics – Lenze E94AYCEO User Manual

Page 44

Advertising
background image

8

Diagnostics

LED status displays

EDK94AYCEO DE/EN/FR/ES/IT 1.0

44

l

H1_Diagnose−RJ45−Statusanzeigen_E94AYCEO

Module status displays

Module status displays are shown by the LEDs ST, ER and DE.

E94YCEO001E

LED

Colour

Status

Description

ST

Green

On

Communication module is supplied with voltage and has a
connection to the standard device.

Blinking

250 ms

250 ms

The communication module is supplied with voltage, but has no
connection to the standard device. (The standard device is either
switched off, in the initialisation phase, or not available).

ER

Red

On

There is an error in the area of the communication module.

DE

Red

On

The communication module is not accepted by the standard device,
or the standard device is not active. (See notes given in the
documentation for the standard device).