8diagnostics – Lenze E94AYCEO User Manual

Page 46

Advertising
background image

8

Diagnostics

LED status displays

EDK94AYCEO DE/EN/FR/ES/IT 1.0

46

l

H1_Diagnose−RJ45−Statusanzeigen_E94AYCEO

Description

Colour / status

LED

Red

Green

LED

MS

Blinking

Off

250 ms

250 ms

CIP module status: "Standby"
The communication module is not fully configured yet, or the
configuration is incorrect.

Blinking

Blinking

250 ms

250 ms

CIP module status: "Device Self Testing"
The communication module is performing a self test.

NS

Off

Off

CIP network status: "No IP Adress"
The communication module is not supplied with voltage or has not
received an IP address yet.

Off

On

CIP network status: "Duplicate IP"
The communication module cannot access the fieldbus (IP address
conflict).

Off

Blinking

250 ms

250 ms

CIP network status: "Connection Timeout"
A time−out is executed.

On

Off

CIP network status: "Connected"
The communication module is working correctly and has
established a connection to the scanner.

Blinking

Off

250 ms

250 ms

CIP network status: "No Connections"
The communication module ...

l

is working correctly;

l

has been assigned an IP address;

l

has not been integrated into the network by the scanner yet.

Blinking

Blinking

250 ms

250 ms

CIP network status: "Self−Test"
The communication module is performing a self test.