Electrical installation

DeviceNet connection

EDK94AYCDN DE/EN/FR/ES/IT 3.0

36

l

H1_E_INST−busltgslaenge

6

Electrical installation

DeviceNet connection

To be able to communicate with the scanner and all other components, the Servo Drives
9400 must be assembled with communication modules.

A DeviceNet line can consist of a maximum of 64 nodes. Nodes are ...
ƒ the connected standard devices;
ƒ the scanner;
ƒ all other components taking part in communication.

Integrating the communication modules into the DeviceNet line requires a PC/laptop with
installed configuration software (e.g. »RSNetWorx«). The PC/laptop serves configuration
and diagnostics purposes only and therefore is no DeviceNet node.

)

Note!

ƒ

Connect a bus terminating resistor of 120

W each to the first and the last

node of the DeviceNet line.

ƒ

Connect the shield at the voltage supply in conjunction with the "V−"
connection to GND once. Select the centre point of the DeviceNet line if
possible.

ƒ

The shield of the DeviceNet cable for each node must only be connected to
the "SHIELD" port of the plug connector.