Electrical installation
DeviceNet connection
EDK94AYCDN DE/EN/FR/ES/IT 3.0
39
l
H1_E_INST−busltgslaenge
Bus cable length
Depending on the baud rate and the cable type used (thick cable/thin cable), the following
bus cable lengths are possible:
Baud rate [kbps]
Bus cable lengths [m]
Thick cable
Thin cable
125
500
100
250
250
500
100
If both thick and thin cable types are used, the maximum cable lengths can be defined
according to the baud rates as follows:
Baud rate [kbps]
Max. bus cable length
125
500 m = L
thick
+ 5 L
thin
250
250 m = L
thick
+ 2.5 L
thin
500
100 m = L
thick
+ L
thin
L
thick
: thick cable length
L
thin