7 commissioning, Possible settings via dip switch, Commissioning 41 – Lenze E94AYCDN User Manual
Page 41: Commissioning
![background image](/manuals/565816/41/background.png)
Commissioning
Possible settings via DIP switch
7
EDK94AYCDN DE/EN/FR/ES/IT 3.0
41
l
H1inbet−bevor
7
Commissioning
Possible settings via DIP switch
E94YCDN001D
Via the DIP switches on the front, the following can be set:
ƒ Station address using switches 1 ... 32 ("MAC ID" area)
ƒ Baud rate using switches 1 and 2 ("Baud" area)
Pos.
Switch positions
Baud rate
Node address (MAC ID)
2
1
kbps
32
16
8
4
2
1
S225
OFF
OFF
125
The station address results from the sum of the
binary values of switches 1 ... 32.
l
Example: Station address 44
W
switches 32, 8, 4 = ON (32 + 8 + 4 = 44)
l
Valid address range: 0 63
l
The Lenze setting for all switches is OFF.
OFF
ON
250
ON
OFF
500
ON
ON
No function
)
Note!
Please observe the information about the setting of the DIP switches given in
the "Commissioning" and "Appendix" chapters of the E94AYCDN
communication manual (DeviceNet).