6 electrical installation, Wiring according to emc, Electrical installation – Lenze E82ZAFPC001 User Manual

Page 50: 6electrical installation

Advertising
background image

6

Electrical installation

Wiring according to EMC

EDK82ZAFPC-001 DE/EN/FR 6.0

50

H1_E_INST-VorgehenVerdraht

6

Electrical installation

Wiring according to EMC

For wiring according to EMC requirements observe the following points:

Note!

ƒ

Separate control cables/data lines from motor cables.

ƒ

Connect the shields of control cables/data lines at both ends in the case of
digital signals.

ƒ

Use an equalizing conductor with a cross-section of at least 16 mm

2

(reference: PE) to avoid potential differences between the bus nodes.

ƒ

Observe the other notes concerning EMC-compliant wiring given in the
documentation for the standard device.

Wiring procedure

1. Observe the bus topology, do not use any stubs.
2. Observe the notes and wiring instructions given in the documents for the control

system.

3. Only use cables corresponding to the listed specifications (53).
4. Observe the notes for the voltage supply of the module (55).
5. Activate the bus terminating resistors on the first and last physical bus device

(65).