Electrical installation

Bus cable length

EDK82ZAFCC−001 DE/EN/FR 5.0

48

l

H2 BusLeitgsLaenge−Leitungslaenge_3

Bus cable length

It is absolutely necessary to comply with the permissible cable lengths.
1. Check the compliance with the total cable length in Tab. 1.

The total cable length is defined by the baud rate.

Baud rate [kbps]

Max. bus length [m]

20

3900

50

1500

125

590

250

250

500

80

Tab. 1

Total cable length

2. Check the compliance with the segment cable length in Tab. 2.

The segment cable length is defined by the cable cross−section used and the number of
nodes. Without repeaters, the segment cable length corresponds to the total cable length.

Node

Cable cross−section

0.25 mm

2

0.5 mm

2

0.75 mm

2

1.0 mm

2

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

Tab. 2

Segment cable length