background image

6

Electrical installation

Bus cable length

EDK82ZAFCC−001 DE/EN/FR 5.0

50

l

H2 BusLeitgsLaenge−Leitungslaenge_3

Check repeater application

Given:

l

Baud rate:

125 kbps

l

Cable cross−section:

0.5 mm

2

l

Number of nodes:

28

l

Cable length:

450 m

Test sequence

Cable length

See

1. Total cable length at 125 kbps:

590 m

From Tab. 1

2. Segment cable length for 28 nodes and a cable cross−section

of 0.5 mm

2

:

360 m

From Tab. 2

3. Comparison: The value under item 2 is smaller than the required cable length of 450 m.

Conclusion

l

It is not possible to use a cable length of 450 m without a repeater.

l

After 360 m (item 2.), a repeater must be installed.

Result

l

The Lenze repeater type 2176 is used (cable reduction: 30 m)

l

Calculation of the maximum cable length:
First segment: 360 m
Second segment: 360 m (according to Tab. 1) minus 30 m (cable reduction when a repeater is
used)

à Maximum possible cable length with repeater: 690 m.

à Thus it is possible to use the required cable length.

)

Note!

The use of another repeater is recommended as

ƒ

Service interface
Advantage: Trouble−free connection during running bus operation is
possible.

ƒ

Calibration interface
Advantage: calibration/programming unit remains electrically isolated.

Advertising