6electrical installation – Lenze E82ZAFCC010 User Manual

Page 50

Advertising
background image

6

Electrical installation

Bus cable length

EDK82ZAFCC-010 DE/EN/FR 5.0

50

H2 BusLeitgsLaenge-Leitungslaenge_3

3. Compare both values.
If the value given in Tab. 2 is smaller than the required total cable length given in Tab. 1,
repeaters must be used. Repeaters divide the total cable length into segments.

Note!

ƒ

Please note the reduction of the total cable length due to the signal delay
of the repeater (see example



50

).

ƒ

There is mixed operation if
– different node devices are connected to the same mains.
– the total cable lengths of the nodes are different at the same baud rate,

the smaller value must be used to determine the max. cable length.

Example: Selection help

Given:

Cable cross-section:

0.5 mm

2

(according to cable specification 44)

Number of nodes:

63

Repeater:

Lenze repeater, type 2176 (cable reduction: 30 m)

At maximum number of nodes (63) the following cable lengths/number of repeaters must
be complied with:

Baud rate [kbps]

20

50

125

250

500

Max. cable length [m]

3900

1500

590

250

80

Segment cable length [m]

310

310

310

250

80

Number of repeaters

13

5

1

-

-

Check repeater application

Given:

Baud rate:

125 kbps

Cable cross-section:

0.5 mm

2

Number of nodes:

28

Cable length:

450 m