Bus cable length

6

EDK82ZAFCC-010 DE/EN/FR 5.0

51

H2 BusLeitgsLaenge-Leitungslaenge_3

Test sequence

Cable length

See

1. Total cable length at 125 kbps:

590 m

From Tab. 1

2. Segment cable length for 28 nodes and a cable cross-section

of 0.5 mm

2

:

360 m

From Tab. 2

3. Comparison: The value under item 2 is smaller than the required cable length of 450 m.

Conclusion

It is not possible to use a cable length of 450 m without a repeater.

After 360 m (item 2.), a repeater must be installed.

Result

The Lenze repeater type 2176 is used (cable reduction: 30 m)

Calculation of the maximum cable length:
First segment: 360 m
Second segment: 360 m (according to Tab. 1) minus 30 m (cable reduction when a repeater is
used)
Maximum possible cable length with repeater: 690 m.
Thus it is possible to use the required cable length.

Note!

The use of another repeater is recommended as

ƒ

Service interface
Advantage: Trouble-free connection during running bus operation is
possible.

ƒ

Calibration interface
Advantage: calibration/programming unit remains electrically isolated.