Protective insulation, Connection terminals, Technical data – Lenze E82ZAFCC210 User Manual
Page 45
Technical data
Protective insulation
4
EDK82ZAFCC-210 DE/EN/FR 4.0
45
H2 Schutzisolierung-PT-klemm AFC210
Protective insulation
Protective insulation between bus and ...
Type of insulation acc. to EN 61800-5-1
8200 vector power stage
Double insulation
Reference earth/PE
Functional insulation
Terminal X3.3/20
No functional insulation
Terminal X3.3/28
Functional insulation
Terminals X3.2/E1 and X3.2/E2
Functional insulation
Connection terminals
X3.2/
E1*
)
Input resistance: 3.3k
0 = LOW (0 ... +3 V), PLC level, HTL
1 = HIGH (+12 ... +30 V), PLC level, HTL
Reference: GND2
*) alternatively frequency input 0 ... 10 kHz, single-track or
0 ... 1 kHz two-track, configuration via C0425
E2
X3.3/
7
Reference potential 1
39
Reference potential 2 for controller inhibit (CINH) at X3.3/28
28
Input resistance: 3.3k
Controller inhibit
Start = HIGH (+12 V ... +30 V)
Stop = LOW (0 V ... +3 V)
20
Voltage: U = 20 V
Load capacity: P = 0.6 W
Reference: GND1