Bus cable length, 6electrical installation – Lenze E82ZAFCC210 User Manual

Page 54

Advertising
background image

6

Electrical installation

Bus cable length

EDK82ZAFCC-210 DE/EN/FR 4.0

54

H2 BusLeitgsLaenge-Leitungslaenge_3

Bus cable length

It is absolutely necessary to comply with the permissible cable lengths.
1. Check the total cable length for compliance with the values provided in Tab. 1.
The total cable length is defined by the baud rate.

Baud rate [kbps]

Max. bus length [m]

20

3900

50

1500

125

590

250

250

500

80

Tab. 1

Total cable length

2. Check the segment cable length for compliance with the values provided in Tab. 2.
The segment cable length is defined by the used cable cross-section and by the number of
nodes. Without repeaters the segment cable length corresponds to the total cable length.

Nodes

Cable cross-section

0.25 mm

2

0.5 mm

2

0.75 mm

2

1.0 mm

2

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

Tab. 2

Segment cable length