Bus cable length

6

EDK82ZAFCC-210 DE/EN/FR 4.0

55

H2 BusLeitgsLaenge-Leitungslaenge_3

3. Compare both values.
If the value given in Tab. 2 is smaller than the total cable length given in Tab. 1, repeaters
must be used. Repeaters divide the total cable length into segments.

Note!

ƒ

Note the reduction of the total cable length due to the signal delay of the
repeater (see example



55

).

ƒ

Mixed operation
– Mixed operation is available if different nodes are operated on the same

mains.

– If the total cable lengths of the participants are different at the same

baud rate, the smaller value must be used in order to determine the
max. cable length.

Example: Selection help

Given:

Cable cross-section:

0.5 mm

2

(according to cable specification 49)

Number of nodes:

63

Repeater:

Lenze repeater, type 2176 (cable reduction: 30 m)

At maximum number of nodes (63) the following cable lengths/number of repeaters must
be complied with:

Baud rate [kbps]

20

50

125

250

500

Max. cable length [m]

3900

1500

590

250

80

Segment cable length [m]

310

310

310

250

80

Number of repeaters

13

5

1

-

-

Check repeater application

Given:

Baud rate:

125 kbps

Cable cross-section:

0.5 mm

2

Number of nodes:

28

Cable length:

450 m