Supply−failure control (L_MFAIL)

2−6

L

Lenze9300Servo.lib EN 1.1

2.1.2

Supply−failure control (L_MFAIL)

If the supply voltage via L1, L2, L3 or +UG, −UG fails, then the drive (drive network) can be decelerated
(braked) in a controlled manner.
Without this function, the drive (drive network) would coast down.

MCTRL_nDCVolt_a

L_MFAIL

nVp

nAdapt_a

nConst_a

nTi

nDCSet_a

nNSet_a

bFault_b

bReset_b

nThreshold_a

nNAct_a

nSet_a

CTRL

0

1

nNOut_a

wRetriggerTime

bStatus_b

bIReset_b

nTn

Abb. 2−6

Supply−failure control (L_MFAIL)

VariableName

DataType

SignalType

VariableType

Note

nAdapt_a

Integer

analog

VAR_INPUT

Dynamic adjustment of the proportional gain of the
U

Gsetp

−control in [%] of

nVp . (16384 º 100 %)

nConst_a

Integer

analog

VAR_INPUT

Proportional gain of the U

Gsetp

controller in [%]

from

nVp . (16384 º 100 %)

nDcSet_a

Integer

analog

VAR_INPUT

Voltage setpoint at which the DC bus voltage is to be
maintained. (1000 V

º 100 %)

nNSet_a

Integer

analog

VAR_INPUT

Speed setpoint in [%] of C0011
(C0011

º 100 % º 16384)

bFault_b

Bool

binary

VAR_INPUT

TRUE = activates the supply−failure control

bReset_b

Bool

binary

VAR_INPUT

TRUE = reset

nThreshold_a

Integer

analog

VAR_INPUT

Restart threshold in [%] of C0011
(C0011

º 100 % º 16384)

nNAct_a

Integer

analog

VAR_INPUT

Comparison value for the restart threshold in [%] of
C0011

nSet_a

Integer

analog

VAR_INPUT

Speed starting point for run−down/deceleration in [%]
of C0011
(C0011

º 100 % º 16384)

nNOut_a

Integer

analog

VAR_OUTPUT

Speed setpoint in [%] of C0011
(C0011

º 100 % º 16384)

bStatus_b

Bool

binary

VAR_OUTPUT

TRUE = supply−failure control is active

bIReset_b

Bool

binary

VAR_OUTPUT

TRUE = supply−failure control active, the drive is
braking

nVp

Integer

VAR CONSTANT RETAIN

Gain

nTn

Integer

VAR CONSTANT RETAIN

Integral−action time T

nTi

Integer

VAR CONSTANT RETAIN

Acceleration time

wRetriggerTime

Unsigned

Integer

VAR CONSTANT RETAIN

Retrigger time

Parameter codes of the instances

VariableName

L_MFAIL1

SettingRange

Lenze

nVp

C0980

0.001 ... 31.000

0.500

nTn

C0981

20 ... 2000 ms

100

nTi

C0982

0.001 ... 16.000 s

2.000

wRetriggerTime

C0983

0.001 ... 60.000 s

1.000