Function block library Lenze9300Servo.lib

Special functions

2.1.2

Supply−failure control (L_MFAIL)

2−11

L

Lenze9300Servo.lib EN 1.1

Parameterization of the supply−failure control

The parameters to be set are strongly dependent on the motor used, the inertia of the driven machine
and the drive configuration (single drive, drive network, master−slave operation, etc.). This function
must therefore be adapted to the individual application in every case.

The following specifications refer to Chapter 2.1.2.1

Important settings prior to the initial commissioning:

Stop!

With internal voltage supply to the terminals, terminal X6/63 is used as a voltage source for external
potentiometers. In this case, measure across terminals +U

G

, −U

G

.

Note!

To perform the measurements, a new download that includes the changes must be made.

1. Measure the DC−bus voltage with an oscilloscope (channel 1)

– with a suitable voltage divider across the terminals +U

G

, −U

G

or

– by providing the DC bus voltage at terminal X6/62, for instance. To do this, connect the

system variable MCTRL_nDCVolt_a with the system variable AOUT2_nOut_a .

2. Measure the speed with an oscilloscope (channel 2)

– by supplying the speed on terminal X6/62, for instance, (standard setting). To do this,

connect the system variable MCTRL_nNAct_a with the system variable AOUT1_nOut_a .

3. Enter, in C0472/20 ( FCODE_nC0472_20_a ) the threshold for the supply−failure detection.

The entry depends on the setting in C0173 (adjsutment of the U

G

−threshold).

– Set the threshold approx. 50 V above the switch−off threshold LU

(example for C0173 = 0.1; C0472/20 = 48 % = 480 V).

Supply voltage range

C0173 =

Switch−off
threshold LU

Switch−on
threshold LU

Switch−off
threshold OU

Switch−on
threshold OU

< 400 V

0

285 V

430 V

770 V

755 V

400 V

1

285 V

430 V

770 V

755 V

400 V ... 460 V

2

328 V

473 V

770 V

755 V

480 V without brake chopper

3

342 V

487 V

770 V

755 V

Operation with brake chopper (up to
480 V)

4

342 V

487 V

800 V

785 V

4. Set the setpoint to which the DC bus voltage is to be controlled:

– Set the setpoint to approx. 700 V (C0472/18 = 70%).

Stop!

This setpoint must be below the threshold of any brake unit which may be connected.If a connected
brake unit is activated, the drive is braked with the maximum possible torque (I

max

). The desired

operating behaviour is lost.