Technical data

Rated data

EDKRBM002 DE/EN/FR 4.0

34

l

H1_Daten−Abm_BL

Rated data

Electrical data

R

B

P

d

Q

B

U

max

[

W

]

[W]

[kWs]

[V

DC

]

ERBM470R020W

470

20

3.0

800

ERBM100R035W

100

35

4.5

R

B

Resistance

P

d

Permanent power

Q

B

Heat quantity

U

max

Max. operating voltage

Temperatures

T

nom

T

TK

T

max

[°C]

On the surface

150

250

500

On the clearance
edge

*)

90

100

120

T

nom

Maximum temperature for rated data

T

TK

Temperature at which the thermal contact is activated

T

max

Maximum temperature in the case of improper use

*)

Measured for air as the ambient medium (small coefficient of
thermal conductivity); if materials which heat up are located
at the clearance edge (greater coefficient of thermal
conductivity), the temperature continues to rise.